Interface Module Im151-1 Standard (6Es7151-1Aa04-0Ab0) - Siemens Simatic ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

Interface modules

10.5 Interface module IM151-1 STANDARD (6ES7151-1AA04-0AB0)

Rated supply voltage of the electronic
components (1L+)
Isolation
Permitted potential difference (to the rail)
Insulation test voltage
Current consumption from rated supply voltage
(1L+)
Power dissipation of the module
Interrupts
Diagnostic function
10.5
Interface module IM151-1 STANDARD (6ES7151-1AA04-0AB0)
10.5
Properties
The IM151-1 STANDARD interface module has the following features:
• It connects the ET 200S with PROFIBUS DP via the RS485 interface.
• The maximum parameter length is 244 bytes.
• The maximum address space is 244 bytes for inputs and 244 bytes for outputs.
• Operation as a DPV0 or DPV1 slave
• A maximum of 63 modules can be operated with the IM151-1 STANDARD.
• The maximum bus length is 2 m.
• Supports option handling and status byte for power modules.
• Firmware update via PROFIBUS DP
• Identification Data
Interface module IM151-1 STANDARD (6ES7151-1AA04-0AB0) replaces the previous
interface module 6ES7151-1AA00-0AB0 to 6ES7151-1AA03-0AB0 compatible.
10-12
Reverse polarity protection
Power failure bypass
Between the backplane bus and electronic
components
Between the PROFIBUS DP and electronic
components
Between the supply voltage and electronic
components
Group error
PROFIBUS DP bus monitoring
Monitoring of the power supply voltage of the
electronics
Voltages, currents, potentials
24 VDC
Yes
No
No
Yes
No
75 VDC, 60 VAC
500 VDC
Approx. 70 mA
Typically 1.5 W
Status, interrupts, diagnostics
None
Yes
Red "SF" LED
red "BF" LED
Green "ON" LED
Operating Instructions, 12/2005, A5E00515771-03