New Information About the "ET 200S Distributed I/O System Manual"
0
4.22 2AO I High Feature Analog Electronic Module (6ES7135-4MB02-0AB0)
4.22
2AO I High Feature Analog Electronic Module
0
(6ES7135-4MB02-0AB0)
Properties
• 2 outputs for current output
• Output range:
• Isolated from the load voltage L+
• Supports isochronous operation
• Supports I&M functions
General terminal assignment
Note
Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules.
Terminal
Assignment Terminal
1
QI
0
2
n.c.
3
M
ana
4
n.c.
A4
AUX1
A3
AUX1
3-18
– ± 20 mA, resolution 15 bits + sign
– 4 to 20 mA, resolution 15 bits
– Minimum time for the synchronous DP cycle (T
– Minimum conversion time of the output modules: (T
Terminal assignment for 2AO I High Feature (6ES7135-4MB02-0AB0)
Assignment
5
QI
1
6
n.c.
7
M
ana
8
n.c.
A8
AUX1
A7
AUX1
QI
: Current analog output, channel n
•
n
M
: Ground of the module
•
ana
n.c.: Not connected (max. DC 30 V can be connected)
•
AUX1: Protective-conductor terminal or potential bus (freely usable
•
up to 230 VAC)
): 0.7 ms
DPmin
): 0.5 ms
WAmin
Notes
Product Information, 03/2006, A5E00743001-01