Wiring The Et 200S; Wiring Rules For The Et 200S; Wiring A Terminal Module With Screw-Type Terminals - Siemens SIMATIC S7 EIP-200S System Manual

Ethernet/ip adapter distributed i/o system
Table of Contents

Advertisement

3.9

Wiring the ET 200S

3.9.1

Wiring rules for the ET 200S

Wiring rules for:
Connectable wire cross-sections for
rigid lines
Connectable wire
cross-sections for
flexible lines
Number of wires per connection
Maximum external diameter of the
wire's insulation
Stripping length of the wires
Wire end ferrules
to DIN 46228
3.9.2

Wiring a terminal module with screw-type terminals

Features
In terminal modules with screw-type terminals, the individual wires are screwed into the
terminal.
No wire end ferrules are required.
Prerequisites
Adhere to the wiring rules.
Tool required
3 mm screwdriver
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
Interface voltage
(supply voltage)
No
Without wire end
0.25 to 2.5 mm
ferrule
With wire end
0.25 to 1.5 mm
ferrule
1 or a combination of 2 wires up to
1.5 mm
ferrule
∅ 3.8 mm
11 mm
Without insulating
Form A, 8 to
collar
12 mm long
With insulating
Form B, up to 12 mm long
collar 0.25 to
1.5 mm
2
Terminal modules
(spring and screw-
type terminals)
0.14 to 2.5 mm
0.14 to 2.5 mm
2
0.14 to 1.5 mm
2
(sum) in a common wire end
2
∅ 3.1 mm at
1.5 mm
2
∅ 3.8 mm at
2.5 mm
2
Form A, up to
12 mm long
Installation and wiring
3.9 Wiring the ET 200S
Terminal modules
(Fast Connect)
0.5 to 1.5 mm
2
2
0.5 to 1.5 mm
2
2
---
2
1
∅ 3.2 mm at
1.5 mm
2
---
---
---
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents