Diagnostics functions
Process interrupts are only sent if the process interrupt mechanism is not overloaded.
*
Measuring principle
Conversion and cycle time
Integration time, can be configured
Resolution
Interference voltage suppression for f = n x (f1 ±
0.5 %), (f1 = interference frequency)
(peak interference value < rated value of input
range)
Crosstalk between the inputs
Operational limit
(in the entire temperature range, with reference to
the input range)
Basic error limit
(operation limit at 25°C)
Temperature error (referenced to the input range) ± 0.003%/K
Linearity error (referenced to the input range)
Repeatability
(in steady state at 25°C referenced to input
range)
ET 200S
Product Information, 03/2006, A5E00743001-01
New Information About the "ET 200S Distributed I/O System Manual"
0
4.13 2AI I 2/4WIRE High Feature Analog Electronic Module (6ES7134-4MB02-0AB0)
Group error
Diagnostic functions readable
Process interrupts
*
Interference frequency suppression in Hz
Conversion time in ms (per channel)
Cycle time of the module in ms (per module)
Common-mode interference (U
Series-mode interference
Status, Alarms, Diagnostics
Red "SF" LED
Yes
Configurable, violation of upper and lower limits
Analog Value Generation
Sigma-Delta
Yes
60
17
18
± 20 mA / 15 bits + sign
4 mA to 20 mA / 15 bits
Interference Suppression, Error Limits
)
Min. 100 dB
SS
Min. 90 dB
Min. -100 dB
± 0.1% with interference frequency suppression
± 0.2% without interference frequency
suppression
± 0.05% with interference frequency suppression
± 0.1% without interference frequency
suppression
± 0.01 %
± 0.01 %
50
None
20
0.04
21
0.5