Wiring Et 200Eco - Siemens SIMATIC ET 200eco Manual

Distributed i/o station
Hide thumbs Also See for SIMATIC ET 200eco:
Table of Contents

Advertisement

Note
The following applies to an ET 200eco with terminal block:
The electronic/sensor power supply 1L+ powers the sensors.
The outputs are powered via by the load voltage supply 2L+.
Protecting components from damage
In order to avoid the destruction of ET200eco components, you must always
provide external line fusing for the electronic/sensor power supply and load
voltage:
• Fusing of the electronic/sensor power supply (1L+):
DC 24 V / 10 A: Tripping characteristics (type) B or C
• Fusing of the load voltage supply: (2L+) 24 VDC / 16 A:
Tripping characteristics (type) B or C
3.4

Wiring ET 200eco

In this
chapter,
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
Wiring procedure
The ET 200eco distributed I/O station is wired in several steps. We recommend
you take the following procedure:
1. Connect ET 200eco to protective earth. See Chapter 3.4.1
2. Wire the I/O module. See Chapter 3.4.2
3. Wiring the terminal block. See Chapter 3.4.3, 3.4.4 or 3.4.5
ET 200eco Distributed I/O Station
A5E00158716-02
How to connect ET 200eco to protective earth (PE)
How to wire I/O modules
How to wire the ECOFAST terminal block
How to wire the M12, 7/8" terminal block
How to loop the PROFIBUS DP and the supply voltage
you will find
Wiring
on page
3-8
3-9
3-19
3-23
3-27