Siemens Simatic ET 200S Operating Instructions Manual page 404

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

New Information About the "ET 200S Distributed I/O System Manual"
0
4.13 2AI I 2/4WIRE High Feature Analog Electronic Module (6ES7134-4MB02-0AB0)
2AI I 2/4WIRE High Feature Technical Specifications (6ES7134-4MB02-0AB0)
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
Weight
Supports isochronous operation
Supports I&M functions
Number of inputs
Cable length
Parameter length
Analog value representation
*
Rated load voltage L+ (from the power module)
Power supply of the transmitters
Galvanic isolation
3-10
Shielded
Is supported if no interference frequency suppression or smoothing is configured.
Reverse battery protection
Short-circuit protection
Between the channels and backplane bus
Between the modules and load voltage L+
Between the channels and PE
Between the channels
Permitted potential difference
Between the channels
Insulation tested
Current consumption
From the load voltage L+
(no sensor supply)
Power dissipation of the module
Dimensions and Weight
15 x 81 x 52
Approx. 45 g
Module-Specific Data
Yes
*
Yes
2
Max. 200 m
12 bytes
S5 and S7 format
Voltages, Currents, Potentials
24 VDC
Yes
Yes
Yes, 60 mA (for both channels)
Yes
No at 2-wire
Yes at 4-wire
Yes
No
140 VDC/100 VAC (with isolated power supply
for the measuring transducer)
500 VDC
48 mA max.
Typically 1.2 W
Product Information, 03/2006, A5E00743001-01