UPS System Installation

Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
S
Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and
installation notes.
S
Do not tilt the cabinet more than
S
Remove the conduit landing plates to add conduit landing holes as required. Plate
material is 16 gauge steel (1.5 mm/0.06" thick).
S
If perforated floor tiles are required for ventilation, place them in front of the UPS.
The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove
the pallet and mechanically install the UPS:
The UPS cabinet is heavy (see Table 3‐1 on page 3-2). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
S
Do not tilt cabinets more than 10° from vertical.
S
Lift the cabinet only with a forklift or damage may occur.
To prevent damage to the wiring channel and wiring in the UPS cabinet base when lifting or moving the
cabinet:
S
Lift and move the cabinet using only the front or rear forklift slots.
S
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
S
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
S
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
W A R N I N G
" 10° during installation.