Figure 6‐21. Path Of Current Through The Upss In Battery Mode – Distributed Bypass - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

UNDERSTANDING UPS OPERATION
Figure 6‐21. Path of Current through the UPSs in Battery Mode – Distributed Bypass
t
6-26
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Bypass Input
UPS Input
Battery
Battery
Battery
Battery
Main Power Flow
If the input power fails to return or is not within the acceptance windows required for
normal operation, the battery continues discharging until a DC voltage level is reached
where the inverter output can no longer support the shared loads. When this event
occurs, each UPS issues another set of audible and visual alarms that indicate a
two-minute SHUTDOWN IMMINENT warning. Unless the system has a valid AC
input soon, redundant UPMs begin shutting down until there are no longer enough
UPMs online to support the connected load. When this event occurs, the system
shuts down. If the bypass source is available, the system transfers to bypass instead
of shutting down.
If at any time during the battery discharge the input power becomes available again,
the rectifier begins to supply DC current to the inverter. At this point, the UPS returns
to Normal mode. If at any time during the battery discharge the AC input power
becomes available again, each rectifier turns on, assumes the inverter load from the
batteries, and begins recharging the batteries. Depending on the total load and the
duration of the battery discharge, battery and rectifier input current limit alarms may
be seen for a short time due to the current required to recharge the batteries.
UPS 1
UPS 2
UPS 3
UPS 4
Breakers
Closed
Open
S
164201701 Rev 4
Tie Cabinet
UPS 1 Output
UPS 2 Output
UPS 3 Output
UPS 4 Output
Critical Load
www.eaton.com/powerquality
Output to

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395

Table of Contents