Chapter 8
Figure
8.1

X-Slot Cards

t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual

Communication

This chapter describes the communication features of the Power Xpert 9395 UPS and
provides information about connecting hardware. For terminal wiring information, see
paragraph 3.2.3 on page 3-17 and paragraph 4.7 on page 4-17. For location of the
customer interface panels and terminals, see Figure 4‐4 on page 4-8 and Figure 4‐13
through Figure 4‐16 starting on page 4-19.
The Power Xpert 9395 UPS has four standard, factory‐installed X-Slot communication
bays. See Figure 4‐13 on page 4-19 for bay locations. The UPS is compatible with the
following X-Slot cards (see Figure 8‐1):
S
Power Xpert
Gateway Card – provides a data gateway from the UPS to the Power
®
Xpert software; provides remote monitoring through a Web browser interface,
e-mail, and a network management system using SNMP; connects to a
twisted-pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the UPS parameters to a Building Management System (BMS). It has
a built-in switching hub that allows one additional network device to be connected
to the network without the requirement of an additional network drop.
S
Modbus Card – provides direct integration of UPS information (meters and status)
to a Building Management System (BMS) using the Modbus RTU protocol.
S
Relay Interface Card (AS/400) – has isolated dry contact (Form-C) relay outputs for
UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass when
interfacing with IBM AS/400 computers, other relay connected computers, and
industrial applications.
S
Industrial Relay Card (IRC) – indicates the operating status of the UPS system
using the customer's monitoring equipment. The IRC uses four isolated
normally-open or normally-closed dry relay contacts to indicate the UPS status.
Online, Bypass, Battery, and Alarm modes can be monitored.
S
Powerware Hot Sync CAN Bridge Card – provides connectivity for operational
mode control and metering of a parallel system at any UPM in the system. In
addition, this card can be used to connect optional system monitoring devices,
such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or
a Supervisory Contact Module II (SCM II) to the UPS.
LAN drops for use with X-Slot connectivity cards must be provided by facility planners
or the customer.
For installation and setup of an X-Slot card, contact an Eaton service representative
(see page 1-10). Refer to the manual supplied with the X-Slot card for user
instructions.
Modbus Card
Relay Interface Card
Power Xpert Gateway Card
Figure 8‐1. Optional X-Slot Cards
S
www.eaton.com/powerquality
164201701 Rev 4
Powerware Hot Sync
CAN Bridge Card
Industrial Relay Card
8-1