8.3

Power Management Software

8.4

Building Alarm Monitoring

8.5

General Purpose Relay Contact

t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
®
Eaton's Intelligent Power
two applications: Intelligent Power
monitoring, and Intelligent Power
operating systems.
®
Eaton's Intelligent Power
manage power devices on your network, even in a virtualised environment. This
innovative software solution combines the most critical applications in ensuring
system uptime and data integrity: not only power monitoring and management, but
also graceful shutdown during an extended power outage.
Because it can manage redundant power systems, it is an ideal solution for the most
critical IT environments with stringent requirements for power availability and
reliability. Yet it is easy to use – the software scales flexibly from a simple
single­computer, single­UPS configuration, to the most sophisticated high­availability
environments."
The software's mass configuration capabilities make installation and maintenance
easy, which minimizes the effort required and benefits the bottom line. Eaton's
cost­effective Intelligent Power Software manages up to ten devices at no charge,
with licences for up to 100 devices – or even an unlimited number – also available.
Contact your Eaton Sales representative for additional information.
This standard feature lets you connect the UPS to your building alarms, such as
smoke detectors or overtemperature alarms. The customer interface terminals for
external connections are located inside the UPS. You should use twisted-pair wires
for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
One general purpose relay contact is provided as a standard feature on the UPS. The
alarm contact is located inside the UPS on the customer interface terminal board.
You can use a normally-closed or normally-open contact. If the state of the contact
changes from the state you specify as normal, a signal is issued. You can connect this
contact to equipment at your facility (such as a light or an alarm bell) to let you know
when an alarm is active on the UPS. This feature is useful if the UPS is located in a
remote area where the UPS horn may not be heard immediately.
Contacts should not be operated in excess of 30 Vac @ 5A maximum.
Software solution, based on Web­2.0 technology, includes
®
Manager™ for UPS management and
®
Protector™, which allows graceful shutdown of
Software gives you all the tools you need to monitor and
C A U T I O N