Figure 5-3. Distributed Bypass System Can And Pull-Chain Simplified Interface Wiring; Figure 5-4. Distributed Bypass System Ups Can Wiring Without Mobs - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

CAN
NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Figure 5‐3. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
NOTE External CAN connections between UPSs require shielded twisted pair wire.
Table 5‐2. CAN Bridge Card Wiring Terminations
From
UPS 1 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
UPS 1
UPS 2
Shielded Twisted Pair
UPS 2
CAN Bridge Card J3
Figure 5‐4. Distributed Bypass System UPS CAN Wiring without MOBs
To
UPS 2 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
INSTALLING OPTIONS AND ACCESSORIES
UPS 3
UPS 4
(If Installed)
(If Installed)
Shielded Twisted Pair
UPS 3
CAN Bridge Card J3
(If Installed)
To
UPS 3 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
S
www.eaton.com/powerquality
164201701 Rev 4
Pull Chain
UPS 4
CAN Bridge Card J3
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)