Figure 3-1. Ups Cabinet Dimensions (Front View) - Eaton Power Xpert Plus 1 Installation And Operation Manual

450–550 kva
Table of Contents

Advertisement

The UPS ventilation requirements are shown in Table 3‐3.
Table 3‐3. Air Conditioning or Ventilation Requirements During Full Load Operation
t
Power Xpert
9395 UPS (450–550 kVA) Installation and Operation Manual
Input/Output
Rating
BTU/hr  1000/ (kg-cal/hr)
Voltage
400/400
450 kVA
480/480
400/400
500 kVA
480/480
400/400
550 kVA
480/480
Figure 3‐1. UPS Cabinet Dimensions (Front View)
UPS INSTALLATION PLAN AND UNPACKING
Heat Rejection
87 (21886)
88 (22107)
Approximately 1652 liter/sec (3500 CFM)
96 (24318)
97 (24563)
Approximately 2478 liter/sec (5250 CFM)
106 (26479)
107 (27020)
Dimensions are in millimeters [inches].
S
www.eaton.com/powerquality
164201701 Rev 4
Ventilation Required for
Cooling Air Exhaust
With Field Installed UPM
3-3