Dd243 Setup - Visonic PowerMaster-10 G2 Quick User Manual

Version 17
Hide thumbs Also See for PowerMaster-10 G2:
Table of Contents

Advertisement

5. PROGRAMMING
Option
06:CONFIRM PANIC
07:RPT CNFM ALRM
08:ENTRY DELAY 1
09:ENTRY DELAY 2
10:ABORT TIME
11:CANCEL ALARM

5.15.4 DD243 Setup

13:OPERATION MOD
Enter the "03:DD243 SETUP" menu to configure DD243 settings.
Option
01:DISARM OPTION
02:ENTRY ALARM
64
Configuration Instructions
A confirmed panic alarm is reported if one of the following occurs within the confirmation time:
a) A second panic device is activated.
b) A second panic alarm on the same device is activated.
c) A tamper event is activated (not from the zone / device that initiated the panic alarm).
Options: in 4/8/12/20 (default)/24 hours and disabled
Define whether the system will report a confirmed alarm.
enable + bypass (default) - The system will report a confirmed alarm and will bypass all
alarmed open zones when the siren ends or when the confirmation timer expires.
disable - The system will not report a confirmed alarm.
enable - The system will report a confirmed alarm.
Two different entry delays allow the user to enter the protected site (while the system is in the
armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Options: 10/15/30(ENTRY DELAY 1 default)/45/60(ENTRY DELAY 2 default) seconds;
3/4 minutes
The PowerMaster can be configured to provide a delay before reporting an alarm to the
monitoring station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY
zones). During this delay period, the siren sounds but the alarm is not reported. If the user
disarms the system within the delay time, the alarm is aborted. You can activate the feature
and select the "Abort Time" interval.
Options: in 00 (default in USA)/15/30 (default)/45/60 seconds; in 2/3/4 minutes
The PowerMaster can be configured to provide a "Cancel Alarm" time window that starts upon
reporting an alarm to the Monitoring Station. If the user disarms the system within that "cancel
alarm" time, a "cancel alarm" message is sent to the Monitoring Station indicating that the
alarm was canceled by the user.
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours.
⋅ ⋅ ⋅
03:DD243 SETUP
Configuration Instructions
Define when it is possible to disarm the system:
entry/wl+awy kp – By the control panel when the system is armed AWAY. By keyfob or
keyprox during entry delay only.
entry/all devs - During entry delay, when the system is armed AWAY, by all devices. When
not in entry delay by keyfob or keyprox only.
entry/DD devs (default) - During entry delay, when the system is armed AWAY, by using the
keyfob or keyprox. Keypads cannot disarm at all.
anytime/all dev – At any time and by all devices.
Define whether the system will report a confirmed alarm during an entry delay (see CONFIRM
ALARM below).
DD243 (default) - An alarm initiated by another detector during the entry delay is not regarded
as a confirmed alarm.
normal mode - The control panel will report a confirmed alarm for the second alarm that is
triggered from a different zone within the confirmation time. There are no alarm restrictions
during entry delay or for the delay zone.
D-304762 PowerMaster-10/30 G2 Installer's Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powermaster-30 g2

Table of Contents