8 Control and electrical connections
Fig. 17 Jumper 1
46
modulated, where the output varies between the minimum and
maximum values on the basis of the value defined by the controller.
Jumper
Input signal
2
[mA]
0 - 3.6*
%
4 - 4.4*
4* - 20
* Dependent on the minimum modulation dept (fan rotation speeds
settings, pre set 20%)
Table 9 Analogue input signal for boiler output

8.6.4 Analogue input (0 - 20 mA)

If this feedback message is received, temperature or heat
output can be selected. The two are described briefly below.
Jumper (1) on the interface is used to select either temperature
( ) or boiler output (%).
Feedback is given in V.
Jumper
Output
1
signal
[V]
0.5
1 - 10
Table 10 Analogue output signal for temperature
Output
Jumper
signal
1
[mA]
0
0.5
%
2.0* - 10
* Dependent on the minimum modulation dept (fan rotation speeds
settings, pre set 20%)
Table 11 Analogue output signal for boiler output
Boiler output
Description
[%]
0 – 20
Boiler off
20 – 22
Hysteresis
20 -100
Desired boiler output
Temperature
Description
[°F]
-
Alarm
50 – 212
Delivered
temperature
Description
Boiler output
[%]
0 - 15
Boiler off
15 - 18
Alarm
20 - 100
Delivered boiler
output
C230 ECO-A