4 Installation

4 Installation
4.1

Standards and certifications

4.2

Regulations governing installation

14
Installation, commissioning, maintenance and repair work must
only be carried out by a suitably qualified specialist.
Installations must conform to national and local codes having
jurisdiction. Canadian installation must conform to CSA B149 &
US installation ANSI Z223.1.
The Gas 230 ECO-A boiler or any of its components do not contain
crystalline silica.
The boiler is certified to use natural gas only with a gas supply of
< 0.5 psig or a gas supply pressure range of 7-14" w.c. [17-35
mbar] max.
The Gas 230 ECO-A boilers are certified with the burner control
unit Comfort Master. Consult local codes having jurisdiction for
other requirements.
All installation must provide a fitted safety relief valve on the boiler
supply piping, without any obstructions or valves. The safety relief
valve needs to be piped to a nearby drain that will avoid personal
injury or damage to property. The relief valve must be sized
according to the minimum relief capacity as listed on the boiler
nameplate. Consult local or national code having jurisdictions
regarding the relief valve piping arrangement.
The condensate is very aggressive and can be harmful to some
drain systems, neutralization of the condensate may be
necessary, consult local codes.
The boiler requires an adequate supply of combustion air, unless
the boiler is a sealed combustion system. The boiler needs a
clean combustion air source according to CSA B149 & ANSI Z223
gas codes.
Installation and maintenance must be done by a qualified
professional, in compliance with prevailing local and national
regulations.
 Gas Installation Code CSA B 149 & ANSI Z223.1 (NFPA 54)
In addition to the above regulations, this boiler must be installed in
compliance with:
 National & local building codes
 ASME CSD-1 as required
 CSA & NEC electrical codes
 Other Regulations
The C230 ECO-A is a CSA certified boiler and must not be modified or
installed in any way contrary to this Installation manual.
Manufacturer's Instructions must NOT be taken as overriding statutory
obligations.