DeDietrich C230 ECO-A 120 Installation, Operating And Service Manual page 69

C230 eco-a series gas-fired condensing hot water boiler
Table of Contents

Advertisement

C230 ECO-A
Code
Description
0
Parameter fault
Maximum flow
1
temperature exceeded
Maximum heat
3
exchanger temperature
exceeded
Maximum heat
4
exchanger temperature
increase exceeded
Maximum difference
between heat exchanger
5
and return temperature
exceeded
Maximum difference
between heat exchanger
6
and flow temperature
exceeded
Waiting time release
8
signal drift
Phase and neutral of
9
mains supply mixed up
10
Shutdown interlock active
Shutdown interlock active
11
or frost protection active
Communication fault with
13
SCU (= optional PCB)
Possible cause
No flow or insufficient
flow
No flow or insufficient
flow during
heat demand
No flow or insufficient
flow
Sensor fault
No flow or insufficient
flow during heat demand
Sensor fault
No flow or insufficient
flow during heat demand
Sensor fault
External cause
Incorrectly set parameter
Bad connection
Mains supply incorrectly
wired
Floating or 2-phase
system
External cause
Incorrectly set parameter
Bad connection
External cause
Incorrectly set parameter
Bad connection
BUS connection
inadequate or non-
11 Control stops and faults
Check/solution
Reset dF and dU
Check:
Flow and/or reason
demand
Check:
Flow (direction, pump, valves)
That the system has been
correctly bled
Temperature sensors for
deviations
Water pressure in the system
Whether the heat exchanger is
dirty
Check:
Flow (direction, pump, valves)
That the system has been
correctly bled
Temperature sensors for
deviations
Water pressure in the system
Whether the heat exchanger is
dirty
Check:
Flow (direction, pump, valves)
That the system has been
correctly bled
Temperature sensors for
deviations
Water pressure in the system
Whether the heat exchanger is
dirty
Check:
Flow (direction, pump, valves)
That the system has been
correctly bled
Temperature sensors for
deviations
Water pressure in the system
Whether the heat exchanger is
dirty
Remove external cause
Check the parameter
Check the connection
Reconnect phase and neutral
Set parameter 32 to 0
Remove external cause
Check the parameter
Check the connection
Remove external cause
Check the parameter
Check the connection
Reconnect
Carry out automatic detection
for heat
69