Setting The Air/Gas Ratio (Maximum Heat Input) - DeDietrich IX 245-130 Installation, User And Service Manual

Floor-standing condensing gas boiler
Table of Contents

Advertisement

Tab.36
Fan speed for gas type G25
Parameter
9524 Required speed LF
9524 Required speed LF
9529 Required speed HF
2441 Fan speed heating max
9512 Required speed ignition
Tab.37
Fan speed for gas type G27
Parameter
9524 Required speed LF
9524 Required speed LF
9529 Required speed HF
2441 Fan speed heating max
9512 Required speed ignition
Tab.38
Fan speed for gas type G31
Parameter
9524
Required speed LF
9524 Required speed LF
9529 Required speed HF
2441 Fan speed heating max
9512 Required speed ignition
Fig.94
Fonction de ramonage
Fonction d'arrêt régulation
Régime manuel
MENU
7702684 - v04 - 05092019
Output
minimum
minimum for boil­
ers in cascade
maximum
ignition
Output
minimum
minimum for boil­
ers in cascade
maximum
ignition
Output
minimum
minimum for boil­
ers in cascade
maximum
ignition
8.4.2
1. Access the function 303 Chimney sweep function.
The Chimney sweep function parameter appears.
2. Turn the
MW-4000282-FR-01
Unit
IX 245–
130
rpm
1550
rpm
1550
rpm
5800
rpm
2500
Unit
IX 245–
130
rpm
1550
rpm
1550
rpm
5800
rpm
2500
Unit
IX 245–
130
rpm
1950
rpm
1950
rpm
5800
rpm
2500

Setting the air/gas ratio (maximum heat input)

button to select Chimney sweep function.
8 Commissioning
IX 245–
IX 245–
IX 245–
150
200
250
1800
1450
1570
1800
1450
1570
6900
5050
6100
2500
2200
2200
IX 245–
IX 245–
IX 245–
150
200
250
1800
1450
1570
1800
1450
1570
6900
5300
6300
2500
2500
2500
IX 245–
IX 245–
IX 245–
150
200
250
2000
1370
1510
2000
1370
1510
6900
5200
5830
2500
2200
2200
IX
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ix 245-150Ix 245-200Ix 245-250

Table of Contents