11 Control stops and faults
Fault
Description Possible
code
Heat exchanger
E:04
temperature exceeded
below normal range
Heat exchanger
temperature exceeded
E:05
above normal range
(high limit thermostat)
Return temperature
E:06
sensor short circuited
Return temperature
E:07
sensor open circuit
Return temperature
exceeded below normal
E:08
range
E:09
Return temperature
exceeded above normal
range
Too great a difference
E:10
between heat exchanger
E:11
and return temperature
E:12
Trap protection activated
72
cause
Bad connection
Defective sensor
Sensor not correctly
mounted
No or too little flow
Bad connection
Defective sensor
Sensor not correctly
mounted
Bad connection
Defective sensor
Sensor not correctly
mounted
Bad connection
Defective sensor
Sensor not correctly
mounted
No or too little flow
Defective sensor
No or too little flow
Sensor not correctly
mounted
Bad connection
Pressure in flue gas
discharge duct is (was)
too high
Air supply obstructed
Check/solution
Check the cable bundle
Replace the sensor if necessary
Check:
flow (direction, pump, valves)
if system has been correctly
bled
temperature sensors for
deviations
if sensor is correctly mounted
water pressure in the system
if heat exchanger is dirty
Check the cable bundle
Replace the sensor if
necessary
Check if sensor is correctly
mounted
Check the cable bundle
Replace the sensor if
necessary
Check if sensor is correctly
mounted
Check the cable bundle
Replace the sensor if
necessary
Check:
flow (direction, pump, valves)
if system has been correctly
bled
temperature sensors for
deviations
if sensor is correctly mounted
water pressure in the system
if heat exchanger is dirty
Replace the sensor if
necessary
Check
:
flow (direction, pump, valves)
if system has been correctly
bled
temperature sensors for
deviations
water pressure in the system
if heat exchanger is dirty
if sensor is correctly mounted
Check the cable bundle
Check that the trap is not
empty; top up if necessary
Blockage in flue gas
discharge/RGA covered
C230 ECO-A