Control Stop - And Fault Memory - DeDietrich C230 ECO-A 120 Installation, Operating And Service Manual

C230 eco-a series gas-fired condensing hot water boiler
Table of Contents

Advertisement

11 Control stops and faults
Fault
Description Possible
code
E:17
Gas valve control fault
Flow temperature sensor
E:32
short circuited
Flow temperature sensor
E:33
open circuit
E:34
Fan fault
E:35
Flow and return swopped
Flame loss occurs 5
E:36
times
Communication fault with
E:37
SU board
Communication fault with
E:38
SCU board (optional)
Shutdown input in
E:39
locked-out mode
Table 20 Fault codes

11.5 Control stop - and fault memory

74
cause
Bad connection
Defective gas valve
Bad connection
Defective sensor
Sensor not correctly
mounted
Bad connection
Defective sensor
Sensor not correctly
mounted
Bad connection
Defective fan
Defective sensor
Wrong flow direction
Bad sensor connection
Sensor not correctly
mounted
Ionization current drops
out
Bad connection
Bad connection
External cause
Incorrectly set
parameter
Bad connection
The boiler control unit has a control stop and fault memory. This
stores the last 16 control stops and the last 16 faults that have
occurred.
With each fault, the following data is saved:
 b or e = control stop or fault code
Check/solution
Check the cable bundle
Replace the gas valve if
necessary
Check the cable bundle
Replace the sensor if
necessary
Check if sensor is correctly
mounted
Check the cable bundle
Replace the sensor if
necessary
Check if sensor is correctly
mounted
Fault in fan cabling
Defect in fan
(Too) much draught over boiler,
so that the fan starts to rotate
Check:
Flow direction
temperature sensors for
deviations
Replace the sensor if
necessary
Inlet gas pressure sufficient?
Inlet gas pressure controller in
order?
Correct gas block operation
and adjustment?
Blockage in air supply or flue
gas discharge?
Flue gas circulation, check flue
gas system for installation
faults and the heat exchanger
for possible leaks
Check SU board is correctly
inserted in the connector on the
PCU-01
Check the cable bundle
Remove external cause
Check the parameter
Check the cable bundle
C230 ECO-A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C230 eco-a 160C230 eco-a 200

Table of Contents