9 Commissioning
50
With a heat demand
1 Boiler starts
2 Burner starts
3 Central heating operation; briefly in part load then in full
load
When a heat demand ceases:
5 Burner stops
6 Boiler stops
0 Stand-by mode
Table 12 Normal operation
9.1.2
Fault during start-up procedure
If nothing appears on the display, check:
the connection of the mains lead;
the main fuse in the instrument box (F = 6.3 AT, 120 V);
the fuse on the control unit (F1 = 1.6 AT, 110 V);
the mains voltage.
A fault code in the display is recognised as follows: the fault
symbol
appears and the fault code flashes underneath it;
The meaning of this fault code can be found in the fault table, see
Section 10.2.
If possible, solve the fault first.
Press the reset key for 3 seconds to restart the C230 Eco-A.
If the display does not show RESET but SERVICE, the boiler must be
switched off and switched on again after 10 seconds before the fault
can be reset.
: