Limiting Input To 115 Kw (Only 4 Section Boilers); Changing Gas; Switching From Gas H To Gas L/Lw And Vice Versa - DeDietrich C 230 ECO Installation And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for C 230 ECO:
Table of Contents

Advertisement

5.4.5

Limiting input to 115 kW (Only 4 section boilers)

1. Press the
key until #CONFIGURATION is displayed.
2. Press
until #LIMITED TEMP. is displayed.
3. Press
until MAX.R.HEAT(%) is displayed.
Set to: 93%.
4. Press
until MAX.DHW(%) is displayed.
Set to: 93%.

5.5 Changing gas

To switch from natural gas H to natural gas L/Lw or propane carry out
the following operations.
5.5.1

Switching from gas H to gas L/Lw and vice versa

If the % of CO
differs from versions C 230-85 ECO and C 230-
2
130 ECO at high stage :
- Check the boiler on low stage
- Check the high stage
- Check the position and measurement of the restriction
03/10/2012 - 300015171-001-01
C 230 ECO
(G27)
LW
10
B
47