5.4.5
Limiting input to 115 kW (Only 4 section boilers)
1. Press the
key until #CONFIGURATION is displayed.
2. Press
until #LIMITED TEMP. is displayed.
3. Press
until MAX.R.HEAT(%) is displayed.
Set to: 93%.
4. Press
until MAX.DHW(%) is displayed.
Set to: 93%.
5.5 Changing gas
To switch from natural gas H to natural gas L/Lw or propane carry out
the following operations.
5.5.1
Switching from gas H to gas L/Lw and vice versa
If the % of CO
differs from versions C 230-85 ECO and C 230-
2
130 ECO at high stage :
- Check the boiler on low stage
- Check the high stage
- Check the position and measurement of the restriction