Settings Scb-10 Print; Setting The 0-10 Volt Input Function Of Scb-10; Analogue Temperature Regulation (°C) - DeDietrich AMC 15 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

Fig.89
AMC 35
40
35
30
25
Q
20
15
10
5
0
0
1000
2000
3000
R
9.4

Settings SCB-10 print

Tab.67
button > Installation Setup > SCB-10 > 0-10 volt input > Parameters
Code
Display text
EP014
SCB func. 10V PWMin
EP030
Min Setp Temp 0-10V
EP031
Max Setp Temp 0-10V
EP032
Min Setp Power 0-10V
EP033
Max Setp Power 0-10V
EP034
Min Setp Volt 0-10V
EP035
Max Setp Volt 0-10V
Fig.90
Temperature regulation
2
1
0
V
3
7686707 - v.01 - 06092018
F=M
4000
5000
6000
7000
AD-3001173-01
Description
Smart Control Board function 10 Volt PWM
input
Sets the minimum set point temperature for 0
- 10 volts for the Smart Control Board
Sets the maximum set point temperature for 0
- 10 volts for the Smart Control Board
Sets the minimum set point power for 0 - 10
volts for the Smart Control Board
Sets the maximum set point power for 0 - 10
volts
Sets the minimum set point voltage for 0 - 10
volts for the Smart Control Board
Sets the maximum set point voltage for 0 - 10
volts
4
AD-3001121-01
M Maximum heat input
F Factory setting
Q Input (Hi) (kW)
R Fan speed (rpm)
9.4.1

Setting the 0-10 Volt input function of SCB-10

There are three options for the 0-10 Volt input control of the SCB-10 print:
disable the input function.
the input is temperature based.
the input is heat output based
9.4.2
Analogue temperature regulation (°C)
1 EP030
2 EP031
3 EP034
4 EP035
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
Tab.68
Temperature regulation
Input signal (V)
Temperature °C
0–1.5
0–15
1.5–1.8
15–18
1.8–10
18–100
9 Settings
Range
0 = Off
1 = Temperature control
2 = Power control
0 °C - 100 °C
0.5 °C - 100 °C
0 % - 100 %
5 % - 100 %
0 V - 10 V
0 V - 10 V
Description
Boiler off
Hysteresis
Desired temperature
AMC