Electrical Specifications; Mains Voltage; Control Box; Fuse Ratings - DeDietrich C230 ECO-A 120 Installation, Operating And Service Manual

C230 eco-a series gas-fired condensing hot water boiler
Table of Contents

Advertisement

8 Control and electrical connections
8.3

Electrical specifications

Fig. 10 Connect mains lead
40
8.3.1

Mains voltage

The boiler is suitable for a 120 V-60 Hz supply with
live/neutral/earth (the control is phase/neutral sensitive). Other
connection values are only acceptable if an isolating transformer
is installed. Connect the mains lead (not supplied) to the 120 V
terminal strip.

8.3.2 Control box

Mains voltage : 115 V/60 Hz
Power consumption at: stand-by/low load/full load:
 C230 ECO-A 80
 C230 ECO-A 120
 C230 ECO-A 160
 C230 ECO-A 200
Safety time
Anti-hunting time
Pump post-circulation time : adjustable between 0 and 98
minutes or continuous (= 99 minutes), set by default to 3
minutes
Max. power consumption of external pump: 300 VA.
8.3.3

Fuse ratings

The 120 V terminal strip contains the fuse F - 6.3 AT.
This is a general fuse for all connected components.
The control unit contains the fuse F1 - 3.2 AT.
This is a fuse for the mains voltage of the control unit, gas multiblock
and ignition, excluding pump.
: 4 / 36 / 125 W
: 4 / 37 / 193 W
: 4 / 53 / 206 W
: 4 / 54 / 317 W
: 3.5 s
: Adaptive 1 - 10 minutes.
C230 ECO-A