7 Flue gas discharge and air supply
26
Sidewall Vented & Direct Vent [Sealed Combustion] Applications
A horizontal vent system with the air supply, required for combustion,
provided within the boiler room or combustion air sources provided
into the room.
7.1.2

Venting options

The standard delivery of the C230 ECO-A boiler can be installed with
any of the venting options listed above. See each respective section
for details; discard the air intake grill when using sealed combustion
vent systems.
7.1.3

Vent Termination Inlet/Outlets

The vent terminals must be installed to provide suitable protection
against wind, rain, snow or blockage along with a rodent/debris
screen. See section 7.1.5, 7.1.6 and 7.1.7 for other requirements.
Conventional chimney application tapered cone (finishing cone), and
sidewall or direct vent require a termination TEE or 90º elbow fitting.
7.1.4

Combustion Air Supply Requirements

The boiler requires a clean, fresh and adequate supply of combustion
air, failure to provide sufficient combustion air supply will result in
carbon monoxide (CO) production that could lead to personal injury
including loss of life or damage to boiler or property. Do not store any
flammable liquids, fluids, vapors or materials near the vicinity of the
boiler.
Special attention
Quality of combustion air
Dust, fumes, corrosive elements, hydrocarbons, other unknown
containments
Paint, beauty, automotive etc. shops
The flue gas vent pipe must be airtight and watertight. Horizontal
sections of the venting must slope downward towards the boiler ½"
per linear foot [42 mm/m] and adequate vent support must be
provided.
Room combustion air supply requirements
The boiler must be provided with an adequate combustion air supply,
the combustion air supply requirements must be determined and sized
in accordance to national and local codes having jurisdiction. CSA
B149 & ANSI Z223.1 – More than one combustion air source may be
required. An optional air intake filter should be fitted air intake housing
(recommendation).
Air supply venting materials
Aluminium, stainless steel or PVC/CPVC (UL 181 or ULc S-110 class
1).
C230 ECO-A