DeDietrich C230 ECO-A 120 Installation, Operating And Service Manual page 73

C230 eco-a series gas-fired condensing hot water boiler
Table of Contents

Advertisement

C230 ECO-A
Fault
Description Possible
code
E:14
5 failed burner starts
5 failed gas leakage
E:15
controls
E:16
False flame signal
cause
No ignition spark
Ignition spark, but no
flame
Flame, but insufficient
ionization
Defective gas valve
No or to little gas
pressure
VPS switch wrongly
adjusted
Bad connection
Defective sensor
Sensor not correctly
mounted
Ionization current has
been measured, while
there may not be a
flame
11 Control stops and faults
Check/solution
Cascade valve does not open
Trap is blocked
Heat exchanger is dirty
Check the air supply
Check:
connection between ignition
cable and transformer
electrode distance, this must
be1/8 - 1/6 inch (3 - 4 mm)
breakdown to earth
condition of the burner set
(burner set/electrode seal)
earthing
bad actuation on SU board
Check:
is the gas cock opened?
is the inlet gas pressure
sufficient?
is the gas pipe vented?
correct gas block operation and
adjustment?
is the air supply or flue gas
discharge blocked?
condition of cable bundle to gas
block
bad actuation on SU board
Check:
condition of the electrode and
earthing
condition of cable bundle
between ignition cable and
transformer
if gas cock is fully opened
if the gas pressure is sufficient
Is the gas cock opened?
Is the gas pressure sufficient?
Are the VPS switches correctly
fitted?
Gas valve is leaking or is stuck
in the open position.
Is the wiring in order, plugs V1,
V2 not mixed up?
Check the VPS settings
Replace the sensor if
necessary
Check if sensor is correctly
mounted
Burner glows as a result of a
high CO
percentage (adjust
2
CO
).
2
Check the ignition / ionization
electrode
Gas valve is leaking or is stuck
in the open position.
73