DeDietrich C230 ECO-A 120 Installation, Operating And Service Manual page 59

C230 eco-a series gas-fired condensing hot water boiler
Table of Contents

Advertisement

C230 ECO-A
Fan speed (rpm)
Boiler type
Full load
230-80
230-120
230-160
230-200
Table 17 Checking and setting values O
Checking and setting values O
Fan speed (rpm)
Boiler type
Minimum load
230-80
230-120
230-160
230-200
Table 18 Checking and setting values O
Fig. 27 Setting values CO
and 230-200
Fig. 28 Setting values CO
and 230-120 (only minimum load)
Checking and setting values O
CO
2
h:3
%
5600
10.0
5600
10.0
6000
10.0
5500
10.0
/CO
for natural gas (front housing removed)
2
2
CO
2
%
L:3
1500
10.5
1400
10.5
1500
10.5
1300
10.5
/CO
for natural gas (front housing removed)
2
2
15.c
15.d
The boiler is supplied with a number of basic settings.
burner control - modulating on the basis of flow temperature
maximum flow temperature - 176°F (80°C)
If other values are required: see Section 8.1.6.
for 230-160
2
15.e
16. Check gas leakage control (VPS if installed):
Then set the gas leakage control pressure switch to a switch
pressure equal to 50% of the inlet pressure. Check that the
measured inlet pressure is not the (higher) closing pressure.
17. Press the reset-key to reset the boiler to 'user level'.
18. Heat the system up to roughly 176°F (80°C) if possible and
switch the boiler off.
19. Vent the system and check the water pressure.
20. The boiler is now ready for operation.
21. Set the boiler control to the required values and write down the
connected type of gas on the boiler type plate: e.g. G290 – 362
psi (25 mbar).
22. Switch the boiler on.
for 230-80
2
/CO
for propane (G31) at full load
2
2
Control
Setting
margin
margin
%
%
± 0.7
n/a
± 0.7
n/a
± 0.5
± 0.3
± 0.5
± 0.3
/CO
for propane (G31) at minimum load
2
2
Control
Setting
margin
margin
%
%
± 0.5
± 0.3
± 0.5
± 0.3
± 0.5
± 0.3
± 0.5
± 0.3
Set minimum load: press the [-] -key and, when L:3
appears in the display, minimum load has been set.
After minimum output has been reached, check the CO
percentage and compare it with the value in Table 18. If the
CO
% level deviates from these values, set the CO
2
percentage using the correction screw of the pressure
controller on the gas block (for the 230-80 and 230-120
models, adjustments are only made at minimum load).
Remove measuring equipment and seal measuring points.
9 Commissioning
Control
Setting
O
2
margin
margin
%
%
%
5.7
± 1.3
n/a
5.7
± 1.3
n/a
5.7
± 0.7
± 0.4
5.7
± 0.7
± 0.4
Control
Setting
O
2
margin
margin
%
%
%
4.9
± 0.8
± 0.5
4.9
± 0.8
± 0.5
4.9
± 0.8
± 0.5
4.9
± 0.8
± 0.5
CO
ppm
< 100
< 100
< 100
< 100
CO
ppm
< 100
< 100
< 100
< 100
2
2
59