Analogue Temperature Regulation (°C); Analogue Output-Based Control; Cascade Control - DeDietrich AMC Pro 45 Service Manual

Control panel & high efficiency wall-hung gas boiler
Hide thumbs Also See for AMC Pro 45:
Table of Contents

Advertisement

7 Installation examples
Fig.31
Temperature regulation
100
90
80
70
60
50
40
30
20
1
10
0
1
2
3
4
5
0 - 10 V
7.5

Cascade control

Fig.32
Cascade numbering
A
Tab.27
> Installation Setup > SCB-10 > Cascade management B > Parameters, counters, signals > Parameters
Code
Display text
NP006
Cascade Type
NP009
CascInterStageTime
NP011
CascadeTypeAlgo
30
AMC Pro
7.4.1
4
3
The 0–10 V signal controls the boiler supply temperature. This control
2
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
Tab.25
6
7
8
9
10
AD-0001156-02
7.4.2
The 0 - 10 V signal controls the boiler output. This control modulates on
the basis of the heat output. The minimum output is linked to the boiler's
modulation depth. The output varies between the minimum and maximum
value on the basis of the value defined by the controller.
Tab.26
With the Diematic Evolution mounted in the master boiler it is possible to
manage up to 7 boilers equipped with the Inicontrol 2 in cascade. The
system sensor is connected to the master boiler. All the boilers in the
cascade are connected by an S-BUS cable. The boilers are automatically
numbered:
B
C
There are two options for cascade control management:
AD-3000964-01
Description
Cascading boilers by adding successively or
in parallel, the boilers function simultaneously
Switch on and switch off timing for the
producer of the cascade
Choice of Cascade Algorithm type, power or
temperature
Analogue temperature regulation (°C)
1 Boiler on
2 Parameter CP010
3 Maximum flow temperature
4 Calculated value
Temperature regulation
Input signal (V)
Temperature °C
0–1.5
0–15
1.5–1.8
15–18
1.8–10
18–100

Analogue output-based control

Control based on heat output
Input signal (V)
Heat output (%)
0–2.0
0
2.0–2.2
0
2.0–10
0–100
A The master boiler is number 1.
B The first slave boiler is number 3 (number 2 does not exist).
C The second slave boiler is number 4; and so on.
Adding supplementary boilers successively (traditional control).
Adding supplementary boilers simultaneously (parallel control).
Description
Boiler off
Hysteresis
Desired temperature
Description
Boiler off
Heat demand
Desired heat output
Model series
0 = Traditional
1 = parallel
1 Min - 60 Min
0 = Temperature
1 = Power
7725087 - v.01 - 06062019