11 Control stops and faults
Code Des
cription
14
Water pressure too low
15
Gas pressure too low
Configuration fault or SU
16 *
not recognised
Configuration fault or
17 *
default parameters table
incorrect
Configuration fault or
18 *
parameter storage unit
(PSU) not recognised
Configuration fault or dF-
19 *
dU parameters unknown
Configuration procedure
20 *
active
Communication fault with
21
SU-01
No flame during
22
operation
24
VPS test failed
70
Possible cause
existent
SCU PCB not present
(any longer) in boiler
Water pressure non-
existent or too low
Incorrect water pressure
parameter adjustment
Water leakage
No flow or insufficient
flow
Incorrect GPS switch
adjustment
Wiring defect or switch
faulty
Incorrect SU PCB for
this boiler
PCU-01 unit parameters
incorrect
Incorrect PSU PCB for
this boiler
Standard briefly
activated following boiler
switch-on
Bad connection
No ionization current
Gas pressure non-
existent or too low
Faulty gas valve
Incorrect adjustment of
the VPS switch
Wiring fault
Faulty VPS switch
Check/solution
Check:
Water pressure in the system
Minimum water pressure
That hydraulic pressure sensor is
properly installed /connected
Check:
That the gas cock is fully opened
That there is adequate gas
pressure
That the GPS switch is properly
installed
Replace the GPS switch if
necessary
Replace SU PCB
Replace PCU-01 unit
Replace PSU PCB
Add/check dF and dU
No action
Check that the PCB is inserted in
the correct connector
Check:
That the gas cock is fully opened
That the gas pressure is sufficient
That the gas block is
appropriately adjusted and
working correctly
Whether the air supply or flue gas
discharge are blocked
The flue gas circulation; inspect
the flue gas discharge system for
installation faults and the heat
exchanger for leaks
Check:
That the gas cock is fully opened
That the gas pressure is sufficient
That the VPS switch is properly
installed
Whether the gas valve is leaking
or in the open position
That the wiring is OK; mix up of
the V1 and V2 plugs
The adjustment of the VPS switch
C230 ECO-A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C230 eco-a 160C230 eco-a 200

Table of Contents