Chapter 2
Rack Installation
This chapter describes the procedure for installing the ETERNUS DX (controller enclosure) in a rack.
Make sure to check "Safety Precautions" before starting the installation. Also refer to the rack manual.
Do
Wear a wrist strap or touch a metal part to discharge the human body's natural
•
static electricity before starting each operation. Failure to discharge static electrici-
ty may cause failure in the ETERNUS DX.
If components are installed in a way other as described in this section, damage
•
and/or device failure or electrical shock may occur.
Do not install the ETERNUS DX in the rack with cables, such as power cords, connec-
•
ted.
The ETERNUS DX contains delicate components, and should be handled gently. Do
•
not drop or knock the ETERNUS DX against the rack when installing it. Also, do not
knock the other devices installed in the rack.
The center of gravity must be taken into consideration to prevent a rack from top-
•
pling over. Enclosures should generally be installed from bottom to top to lower
the center of gravity and to ensure the safe use of racks.
Do Not
Do not uninstall the drives that are installed by default or move them to any other
•
slot.
Contact your sales representative or maintenance engineer if drives that are instal-
led by default need to be uninstalled or moved to another slot.
FUJITSU Storage ETERNUS DX200F All Flash Array Configuration Guide (Basic)
Copyright 2014 FUJITSU LIMITED
16
P3AM-8462-01ENZ0