Fire Control Panel MAG8 - Installation and Operation Manual

3. Initial Power-up of MAG8 Panel

ATTENTION: It has been assumed that prior to making the connection
!
at the panel, the integrity of the system ALL wiring has been
comprehensively tested, including insulation to earth.
• Connect the battery leads from the power supply box to the positive and negative
battery terminals.
• Switch on the mains power supply.
• If the buzzer and indicator LED's are operating, press the RESET button.
• The panel must be in Normal Operation Mode - only POWER SUPPLY 230V will be
illuminated. NOTE: The "Battery Low" LED might light on initially until the battery is
charging up to the required level.
If in Normal Operating Mode other LED's are illuminated and the buzzer is
sounding, carefully check all fuses and connections. Refer to the Faults and
System status LED description and the connection diagram on the inside of
the external cover will assist in identifying the trouble.
!
ATTENTION: Do not short out the battery terminals because any
internal protection will switch on and the panel will stop function!
If by some chance the fault will not cancel, and only on the advice of our Technical
support Department, return the PCB CHAssIs ONLY to your supplier. DO NOT
return the metal / plastic box.

4. Connecting the Zone Circuits

• Disconnect the mains power supply and the battery connection.
• Remove the EOL-module from the Zone 1 terminal on the main module and fit it to the
last detector of the Zone 1 circuit as observe the polarity:
• Ensure all terminations are made correctly and all detector heads are set into their
bases.
• Connect Zone 1 circuit to the panel terminal block.
• Power up the panel with the mains and battery.
• Press "
RESET" button.
• The panel is in Normal Operation Mode - only POWER SUPPLY 230V lights on.
If General Fault and zone 1 FAULT LED's illuminate, there is a wiring/
connection problem. Check the polarity of the connection, the connection of
the devices and whether a head is removed. Check the EOL proper polarity
and position.