3. Testing the MAG2/4 fire panels

ATTENTION: It has been assumed that prior to making the connection
!
at the panel, the integrity of the system ALL wiring has been
comprehensively tested, including insulation to earth.
• Switch on the mains power supply.
• Connect the battery leads from the black power supply box to the positive and
negative battery terminals.
• If the buzzer and indicator LED's are operating, press the RESET button.
In Normal Operating Mode only POWER SUPPLY 230V will be illuminated.
NOTE: The battery might show a 'Low Battery Fault' initially until it has had time to
charge up to the required level.
If other LEDs are illuminated and the buzzer is sounding, carefully check all
fuses and connections. Refer to the page 7 for the associated yellow LED's
apply to. The connection diagram on the inside of the external cover will assist
in identifying the LED.
!
ATTENTION: Do not short out the battery terminals because an internal
protection will switch on and the panel will stop function!
If by some chance the fault will not cancel, and only on the advice of our Technical
support Department, return the PCB CHAssIs ONLY to your supplier. DO NOT
return the metal / plastic box.
4. Connecting the zones circuits
• Disconnect the mains power supply and the battery connection.
• Remove the EOL-module from the zone 1 terminal on the main module and fit it to the
last detector of the zone 1 circuit as observe the polarity:
• Ensure all terminations are made correctly and all detector heads are plugged into their
bases.
• Connect Detector circuit ONE to the panel terminal block.
• Power up the panel with the mains and battery.
• Press RESET button.
The panel should be in the 'NORMAL MODE'.
If General Fault and zone 1 FAULT LED's illuminate, there is a wiring/
connection problem. Check the polarity of the connection, the connection of
the devices and whether a head is removed. Check the EOL proper polarity
and position.