Automatic operation (Kerys in "AUTO" mode) (temporary "grid return" coupling)
Loss of grid voltage
Adjustable grid loss acquisition delay (controlled by the Kerys or by a mains detection module).
Generating set start request.
The speed and voltage of the generating set increase.
Power unit switched on, grid side.
Generating set power unit switched off after voltage and frequency stabilisation.
Return of grid voltage
Adjustable grid return acquisition delay (controlled by the Kerys or by a mains detection module).
Synchronisation of the generating set to the grid.
After synchronisation, the grid power unit is switched off.
Transfer of the active and reactive power of the generating set to the grid according to a predetermined ramp. The ramp
does not exceed 10 seconds for transfer of the generating set's rated output. The generating set power unit is disconnected
when the power on the generating set reaches the lower limit.
Generating set power unit switched on.
Cooling delay.
Generating set stopped and set to standby.
FORCED OPERATION (Kerys in "AUTO" mode) (temporary outward and return coupling)
Start of FORCED OPERATION
Generating set start request.
The generating set voltage and speed increase.
When the generating set is stabilised in speed and voltage, synchronisation of the generating set to the grid is requested.
After synchronisation, the generating set power unit is switched off.
Transfer of the active and reactive power from the grid to the generating set according to a predetermined ramp. The ramp
does not exceed 10 seconds for transfer of the generating set's rated output. The generating set power unit is disconnected
when the power on the generating set reaches the lower limit.
Power unit switched on, grid side.
End of FORCED OPERATION
Opening of the forced operation order.
Synchronisation of the generating set to the grid.
Grid power unit switched off.
Transfer of the generating set's active and reactive power to the grid.
Generating set power unit switched on.
Cooling delay.
Generating set stopped and set to standby.
Manual generating set operation
This mode of operation is selected with the "MANU" key. The operator is able to start and stop the generating set via the MMI
keypad. The power unit is switched off manually with the manual synchronisation of the generating set to the grid using the keys
"+ F", "- F", "+V", "-V", the load transfer remains automatic. The safety devices of the generating set remain active in this mode of
operation.
The Kerys remains in "AUTO" mode
The installation is supplied by the generating set
The Kerys remains in "AUTO" mode
The installation is supplied by the grid
This mode of operation is the responsibility of the operator