SDMO R 340 U User And Maintenance Manual page 47

Table of Contents

Advertisement

Generating set started
Screen no.
G 8
Default
screen
24/08/2005
G 9
24/08/2005
G 10
24/08/2005
Generating setstop
Screen no.
G 11
24/08/2005
Screen
AVAILABLE POWER
75%
13:12
AUTOMATIC STOP
IN PROGRESS
LOAD SUPPRESSION
1 min 30 sec
13:12
AUTOMATIC STOP
IN PROGRESS
COOLING DOWN
1 min 30 sec
13:14
Screen
OFF
IN PROGRESS
13:16
Operating phase – generating set in operation – stable
voltage and frequency
Available power
Date and time (depending on settings)
Operating mode - operation in Auto Mode
Opening of power supply device (motorised circuit breaker
or source changeover switch controlled by TELYS)
Countdown for the mains return delay OR the load test
delay
Date and time (depending on settings)
Operating mode - operation in Auto Mode
Generation set cooling in progress
Countdown for Engine Stop delay (cooling) OR Gradual
Stop delay (Coolant temperature) OR Overload Gradual
Stop delay OR OFF load test delay
Date and time (depending on settings)
Generating set stop in progress
Date and time (depending on settings)
45/285
Data displayed
Data displayed