6.3.1.2.

Conformity to legal and regulatory requirements

The various components of the system comply with the following standards:
Requirements specific to programmable controllers:
(Functional characteristics, immunity, robustness, safety, etc.)
EN 61131-1/2/3 (IEC 1131-2, IEC 664), EN61326,
CSA 22-2,
UL508.
Compliance with European directives (low voltage, electromagnetic compatibility, machinery). CE marking in
application of the safety requirements of standard EN 61131-2 – Programmable controllers, Part 2 – Equipment
requirements and tests.
To obtain the specific information prescribed by EN 61131-2, refer to the appropriate sections of that publication.
Electrical and self-extinguishability properties of insulating materials:
UL 746C,
UL 94.
Pollution degree: 2
Mechanical strength (details):
Vibration resistance:
Frequency range:
Continuous vibrations:
Occasional vibrations:
Frequency range:
Continuous:
Occasional:
Complies with standard IEC 68-2-6, test Fc
Shock resistance
Occasional shocks:
Complies with standard IEC 68-2-27, test Fa
Emissions: Complies with standard EN55022 class A
Variation in supply voltage: EN61131-2 §6.3.7.3
Immunity:
Complies with standard IEC 61000-4-2:
Complies with standard IEC 61000-4-3
Complies with standard IEC 61000-4-4:
Complies with standard IEC 61000-4-5:
Complies with standard IEC 61000-4-6:
Complies with standard IEC 61000-4-8:
EN 61131-2 1994 (§2.1.3.2),
10 - 57 Hz,
0.0375mm amplitude,
0.075mm amplitude.
57Hz - 150Hz,
0.5 g constant acceleration,
1 g constant acceleration.
15g, 11ms, semi-sinus.
Electrostatic discharge: 4 kV for contact discharge, 8 kV for air discharge.
Radiated field at 10V/m from 80MHz to 1GHz with sinusoidal modulation
AM 1kHz.
Rapid transients in waves of 2 kV on power cables, 1 Kv on signal cables.
Shock waves of 2 kV between wires and ground, 11 kV between wires for
the supplies and 1kV relative to ground for long signal circuits (lines from a
building or from a distance of over 30 m).
Immunity to current injected at 3V from 150 kHz to 80 MHz (could be
increased to 10V).
Immunity to the magnetic field at the grid frequency at 30 A/m.
54/285