During saving, the following screen indicates that the operation in is progress:

6.3.4 Configurations

6.3.4.1.

Operating principle

The operational modes are as follows:
SOLO
Genset
Power plant
Note:
Without coupling: the switch is equipped with electrical and mechanical interlocking.
With coupling: the switch is not equipped with an electrical and mechanical interlock.
Saving in flash...
Without
Without N/E
coupling to
grid
Temporary
With coupling
to grid
Without N/E
Without
coupling to
grid
Without N/E
- Operation of a single genset without coupling.
- Normal/emergency switch (NES) not controlled by Kerys.
switch
(A612)
- Automatic operation of a single genset.
coupling
- Temporary coupling on grid return following interruption.
(A651)
- Operation of a power plant without coupling to grid.
switch
- Normal/emergency switch (NES) not controlled by Kerys.
(A632)
- Power plant gensets interconnected by parallel lines.
- Operation of a power plant without coupling to grid.
switch
- Normal/ermegency switch (NES) not controlled by Kerys.
(A633)
- Power plant genset interconnected by CAN.
67/285