9. After return to the KERYS home screen,
The configuration will only be taken into account if the following operations are carried out:
Important
Power plant Without common part and without inverter (A632-A633)
1. Turn off the battery isolator switch.
2. Check that the emergency stop buttons are activated.
3. Press the "STOP" button on the KERYS.
4. Turn the changeover switch to position 2.
1: SOLO GENERATING SET WITHOUT GRID COUPLING
APPLICATION: A612
2: PRODUCTION POWER PLANT WITHOUT GRID COUPLING
APPLICATION: A632 / A633
3: NOT APPLICABLE
4 : SOLO GENERATING SET WITH GRID COUPLING
APPLICATION: A651
Choix configuration centrale loueur
A632: Power plant without shared switching unit without Normal/Emergency parallel line
A633: Power plant without shared switching unit without Normal/Emergency Digital Bus
5. Select the configuration " A632: Power plant without shared switching unit without Normal/Emergency parallel line" by
directly clicking on the touch screen.
Select the configuration " A633: Power plant without shared switching unit without Normal/Emergency Digital Bus" by
clicking directly on the touch screen.
N.B. selecting detection depends on the connection made according to Section 5. "Connections of
the generating sets".
Important
Turn on the battery isolator switch.
Wait 5 seconds.
Turn off the battery isolator switch.
(If the switch is already set to " 2 ", turn the switch and return to position '' 2 '')
After changeover, the screen below appears.
4
98/285
1
2
3