Earth Connection - Aastra AXD Installation And Maintenance Manual

Aastra 5000 server installation and maintenance manual
Table of Contents

Advertisement

6.2.1.5

Earth connection

Connect the cabinets' earth connectors (see Figure 3.1) to the security earthing system
via a 16 mm2 yellow/green cable.
6.2.1.6
Electrical power supply
On the installation site, provide one socket for each cabinet (main and extension), and
one socket for the administration console.
Each socket must support the nominal voltage of 230 V CA (or 115 V depending on type
of installation) in 50 Hz/60 , the current intensity of 10/16 A and must have a third
earthing conductor to ensure protection against discharges, electric shocks, and to avoid
electromagnetic interference. The power outlets installed must comply with the standard
NF C-15100.
Make sure there are sufficient sockets for other equipment as required.
Nota :
Do not use an extension cable between the power source and the iPBX power
supply module(s).
6.2.1.7
Equipment identification
Equipment for the new system is delivered in individual boxes. To complete a checklist of
the delivered equipment, look for the package labelling and enter this information.
An example of the labelling on the packages is given below:
AMT/PTD/PBX/0058/4/6/EN
Page 312
01/2011
Risk of fire and electrical shock
To protect against risk of fire and electrical shock:
make sure there are no screws, tools, or any metal items inside the cabinets.
make sure the system is connected to a socket with an grounding conductor.
For the safety of the installers, the iPBX must be connected to a 3-wire power point
connected to the general ground of the building.
Use only three-conductor (male and female) connectors: two phase conductors
and one grounding conductor.