Removing the Air Duct
EQUATION 4-1
4.4.2
Installing the Air Duct
Caution – When the server is in operation, ensure that the air duct is correctly
installed to prevent the system from overheating.
1. Install the air duct into the chassis as shown in
Ensure that the air duct is aligned and fully seated in the chassis.
2. Re-install the memory tray.
See
3. Install the top cover.
See
4. Slide the server into the rack.
See
5. Reconnect the power cord (or cords) to the power supply (or supplies).
Verify that the AC Present LED is lit.
See
4-18
Sun Fire X4450 Server Service Manual • November 2009
Section 4.2.2, "Installing the Memory Tray" on page
Section 6.1, "Installing the Top Cover" on page
Section 6.3, "Returning the Server to the Normal Rack Position" on page
Section 6.4, "Powering On the Server" on page
.
FIGURE 4-10
4-13.
6-2.
6-5.
6-4.