Vertical Terminations (Top &Rear Vent) - kozy heat 56701 Installation And Operation Manual

Direct vent fireplace
Table of Contents

Advertisement

ALL RIGID PIPE APPLICATIONS
KOZY HEAT #700 SERIES
VERTICAL TERMINATIONS (top vent)
MAXIMUM: 33 ft. (10.06m) + cap.
NOTE: Flange on top stand-off must be bent upwards to a 90˚ angle when top venting.
VERTICAL TERMINATIONS (rear vent)
MINIMUM: 90˚ elbow +14" ( 356mm) + cap.
MAXIMUM: 90˚ elbow + 22 ft. (6.71m) + cap.
RESTRICTOR
A restrictor is included in fireplace components packet.
Each installation is unique and affected by various factors including venting configuration, altitude and climate. Therefore, after
fireplace installation is complete a restrictor may be required or may need to be removed or modified.
Please refer to page 22 for installation instructions if installing restrictor in conjunction with venting.
Page 51 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after
venting is completed.
HORIZONTAL & VERTICAL COMBINATION TERMINATIONS (top vent)
MAXIMUM: 10 ft. (3.05) horizontal + 20 ft. (6.10 m) vertical + cap. 30 ft (9.14m) total.
NOTE: Flange on top stand-off must be bent upwards to a 90˚ angle when top venting.
ELBOWS
For each additional 90° elbow used after first elbow, 3 ft. (914 mm) must be subtracted from maximum allowed venting.
For each 45° elbow used, 1-1/2 ft. (457 mm) must be subtracted from maximum venting allowed.
NOTE: (2) 45° degree elbows may be used in place of (1) 90° elbow.
VENTING
VERTICAL VENT SYSTEM CLEARANCES
TOP
1 inch (25 mm)
PAGE 21
BOTTOM
1 inch (25 mm)
DO NOT USE FOR VERTICAL TERMINATIONS
SIDES
1 inch (25 mm)