OPERATION

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The alarm
sounds and the
Bypass mode when:
S
S
S

Standby Mode

When the UPS is turned off and remains plugged into a power outlet,
the UPS is in Standby mode. The
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE For 200–240V models, the output receptacles may remain electrically live (up to
100–120V). Unplug the UPS to ensure power is not available to the output receptacles.
36
EATON Powerware
ware.com
μ
indicator illuminates red. The UPS transfers to
The UPS has an overtemperature condition.
The UPS has an overload condition of 103 to 110% for 30 seconds.
The UPS detects a fault in the battery or UPS electronics.
®
5125 Two-in-One UPS (2400/3000 VA) User's Guide
μ
indicator flashes and the load level
S
164201383 Rev C www.power-