Table 7. Battery
UPS Configuration
EBM Configuration
Type
Charging
External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to 90% usable capacity at nominal line voltage after full load discharge; an external
charger is recommended for faster recharge times when using more than two EBMs.
Monitoring
Advanced monitoring for earlier failure detection and warning; auto detection of additional
EBMs (if using Powerware LanSafe Power Management Software, the ERM configurator tool
Table 8. Battery Runtimes (in Minutes at Full/Half Load)
Model
UPS Internal Batteries
2400 VA
7/19
3000 VA
5/15
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
®
EATON Powerware
5125 Two-in-One UPS (2400/3000 VA) User's Guide
(10) 12V, 5 Ah internal batteries
PW5125 120 EBM: 120V, 30A
Sealed, maintenance-free, valve-regulated, lead-acid
Internal battery: less than 3 hours to 90% usable capacity
at nominal line voltage after full load discharge
must be used for accurate reporting of EBM battery times).
+1 EBM
+2 EBMs
35/73
60/124
25/61
49/103
SPECIFICATIONS
+3 EBMs
+4 EBMs
85/177
110/229
69/146
90/190
S
164201383 Rev C www.power-
ware.com
57