Model Specifications EMEA

Table 11. Electrical Input Connections
Model
9PX6KIRTN-L
Table 12. Electrical Output
All Models
Voltage Regulation
Efficiency
Frequency Regulation
Nominal Output
Frequency
Output Overload
Output Overload ( Bypass Mode )
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Ratio
Output Short Circuit
Table 13. Electrical Output Connections
Model
9PX6KIRTN-L
40
Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01
Input Connection
Hardwired
Normal Mode
±1%
> 98% (High Efficiency mode)
>93%
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
200/208/220/230/240V (voltage configurable)
6000VA / 5400W*
50 or 60 Hz, autosensing or configurable as a frequency converter
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 500ms
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online Mode: 0ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Up to 0.9
Up to 3:1
max RMS & delay time: 56.5A/150ms; The max peak value: 92A
Output Connection
Hardwired
(2) IEC C19
(8) IEC C13

Battery Mode

±1%
> 91%
±0.5% of auto-selected nominal
frequency
Output Cable
(2) IEC 10A