Powerware 5125 Two-in-One UPS
®
2400/3000 VA
User's Guide

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Powerware 5125

  • Page 1 Powerware 5125 Two-in-One UPS ® 2400/3000 VA User’s Guide...
  • Page 2 VCCI Notice Powerware, ABM, X-Slot, LanSafe, and FERRUPS are registered trademarks and ConnectUPS is a trademark of Eaton Electrical Inc. Modbus is a registered trademark of Modicon. AS/400 is a registered trademark of International Business Machines Corp. ECopyright 2002–2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be...
  • Page 3 92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact: Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland...
  • Page 4 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
  • Page 5: Table Of Contents

    ............. . . ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power-...
  • Page 6 ..........® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power-...
  • Page 7: Introduction

    — causing hours of lost productivity and expensive repairs. With the Powerware 5125, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The Powerware 5125 is designed for critical applications such as PCs, servers, workstations, and telecommunications equipment.
  • Page 8 Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring. Sequential shutdown and load management through separate receptacle groups, called load segments. Backed by worldwide agency approvals. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 9: Safety Warnings

    To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 2.5 milliamperes. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 10 I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 2,5 milliampere. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 11: Belangrijke Veiligheidsinstructies

    Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 12 Houd onbevoegden uit de buurt van de accu’s. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 13 Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 14 Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 2,5 mA. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 15 Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 16: Avvisi Di Sicurezza

    ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 17 Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 18: Viktig Sikkerhetsinformasion

    Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total lekkasjestrøm enn 2,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 19 Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto removerá o aterramento de segurança da UPS e do equipamento conectado. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 20 В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 21 Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь к местным нормативным актам за информацией о требованиях к утилизации. Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 22: Advertencias De Seguridad

    Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 2,5 miliamperios. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 23 UPS:ens anslutning). Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen från både UPS-enheten och den anslutna utrustningen. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 24 Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 25: Installation

    NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 26: Connecting The Ups Internal Battery

    Figure 3. Connecting the Internal Battery Connector Install the UPS front cover (see Figure 4). Figure 4. Installing the UPS Front Cover Continue to the following section, “UPS Setup.” ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 27: Ups Setup

    INSTALLATION UPS Setup The Powerware 5125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, “Rack-Mount Setup;” otherwise, continue to “Tower Setup” on page 22.
  • Page 28: Tower Setup

    Unscrew and remove the mounting brackets on each side of all cabinets as shown in Figure 7. Mounting Bracket Figure 7. Removing the Mounting Brackets ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 29 Carefully position the cabinet upright with the air vents at the top (see Figure 9). Continue to “Installing the UPS” on page 27. Air Vents Figure 9. Pedestals with One Cabinet ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 30 Align the pedestals with the screw holes on the end of the EBM cabinet. Secure the pedestals with the screws provided in the accessory kit. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 31 NOTE Pedestals are required for installations with one or two cabinets. Joining brackets are required for installations with two or more cabinets. Air Vents Figure 13. Tower Setup with Three Cabinets ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 32 Figure 14. Installing the Joining Brackets (Top View with Pedestals) 12. If installing additional EBMs, repeat Step 11 for each cabinet. 13. Continue to the following section, “Installing the UPS.” ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 33: Installing The Ups

    Output Receptacles Communication Port Circuit Breakers UPS Battery Connector EBM Cable EBM Battery Connectors Battery Circuit Breaker Figure 15. Typical UPS Installation with Two EBMs ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 34 UPS is in Standby mode with the equipment offline. If the alarm beeps or a UPS alarm indicator stays on, see Table 9 on page 60. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 35: Remote Emergency Power-Off Installation

    NOTE If more than two EBMs are installed, an external battery charger is recommended for faster recharge times. Remote Emergency Power-off Installation The Powerware 5125 includes a REPO port that allows power to be switched off at the UPS output receptacles from a customer-supplied switch in a remote location.
  • Page 36 –0.5 mm (18–20 AWG). NOTE A separate contact must simultaneously cause UPS input AC power to be removed. Pin 1 Pin 2 Figure 16. REPO Connector ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 37: Ups Rear Panels

    (approximately one second). Activate the external REPO switch to test the REPO function. De-activate the external REPO switch and restart the UPS. UPS Rear Panels This section shows the rear panels of the Powerware 5125 models. Communication Port 5-15 Receptacles Circuit Breakers...
  • Page 38 IEC 320-C13 Receptacles X-Slot Communication Circuit Breakers Ground Bonding Screw REPO Port IEC 320-C19 Receptacle Battery Connector Figure 20. 3000 VA, 200–240V (PW5125 3000g RM) Rear Panel ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 39: Operation

    To turn on the UPS without using utility power, press and hold the On button for at least four seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 40: Turning The Ups Off

    Unplug the UPS. If you do not unplug the UPS, it remains in Standby mode. Operating Modes The Powerware 5125 front panel indicates the UPS status through the UPS indicators. Figure 21 shows the UPS front panel indicators and controls.
  • Page 41: Normal Mode

    When utility power is restored after the UPS shuts down, the UPS automatically restarts. The indicator flashes until the battery has recharged to an acceptable level. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 42: Bypass Mode

    NOTE For 200–240V models, the output receptacles may remain electrically live (up to 100–120V). Unplug the UPS to ensure power is not available to the output receptacles. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power-...
  • Page 43: Configuration

    Press the button to confirm the selection and exit Configuration mode. If you do not press the button, the UPS defaults to the original settings. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 44 Press the Off button ONCE to Press the Alarm Reset button select an option. to save the setting and exit Configuration mode. Figure 23. Using Configuration Mode ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 45 * For 100, 200, or 208V models, Site Wiring Fault is not available (flashing is the only status). ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 46 CONFIGURATION ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 47: Additional Ups Features

    X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 5125 is factory-installed with a Single-Port Card, which can be replaced with one of the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
  • Page 48: Single-Port Card

    USB Card Figure 24. Optional X-Slot Cards Single-Port Card The Powerware 5125 is factory-installed with a Single-Port Card, enabling connection to a PC for power management control or to the Powerware Expansion Chassis for multiple communication options. To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
  • Page 49 Figure 26. Removing the Single-Port Card Move the J3 jumper to the AS/400 position to enable the ® On-Bypass relay as shown in Figure 27. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 50 Align the Single-Port Card with the slot guides and slide the card into the slot until it is firmly seated. Secure the Single-Port Card with the screws removed in Step 1. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 51: Load Segments

    Figure 28. UPS Load Segments (120V Model Shown) Load Segment 2 Load Segment 1 Load Segment 3 Figure 29. UPS Load Segments (PW5125 3000g RM) ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 52 ADDITIONAL UPS FEATURES ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 53: Ups Maintenance

    Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 54: Replacing The Electronics Module

    Remove the two screws on the left of the electronics module. Remove the electronics module and retain the screws (see Figure 31). Figure 31. Removing the Electronics Module ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 55: When To Replace Batteries

    When the indicator flashes and the audible alarm beeps once every five seconds, the batteries may need replacing. Contact your service representative to order new batteries. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 56: Replacing Batteries

    To replace the UPS internal batteries: Remove the UPS front cover by pulling on both ends (see Figure 32). Figure 32. Removing the UPS Front Cover ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 57 Figure 34. Removing the Battery Slide the new battery into the UPS. Reinstall the battery retaining bracket and nuts removed in Step 2. Replace the UPS front cover. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 58: How To Replace Extended Battery Modules

    Figure 35. 10. Remove the breaker tie from the circuit breaker on all EBMs. 11. Switch all battery circuit breakers to the ON ( ) position. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 59: Recycling The Used Battery Or Ups

    C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 60 UPS MAINTENANCE ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 61: Specifications

    48.3 x 62.2 x 8.9 cm (WxDxH) 19.0” x 24.5” x 3.5” (2U) 19.0” x 24.5” x 3.5” (2U) Weight 37 kg (82 lb) 54.9 kg (121 lb) ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 62 Agency Markings cULus, cUL cULus, cUL, UL-GS, CE TÜV-GS (model dependent) EMC (Class A) FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003 ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 63 60/124 85/177 110/229 3000 VA 5/15 25/61 49/103 69/146 90/190 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 64 SPECIFICATIONS ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 65: Troubleshooting

    If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 66 50. The Extended Battery Module Switch all the battery circuit breakers to the (EBM) battery circuit ON position. breakers are in the OFF position. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 67 UPS. Check for one of the following alarms: Overtemperature, Overload, UPS Failure, or Battery Service. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 68 UPS fault condition. Save your work and turn off your equipment. Turn off and unplug the UPS. Contact your service representative. The alarm cannot be silenced. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 69: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 70 TROUBLESHOOTING ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 71: Warranty

    Two-Year Limited Warranty (US and Canada) Powerware UPS Models: 5110, 5115, and 5125 WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Powerware 5110, 5115, and 5125 Products (individually and collectively, the “Product”) purchased on or after...
  • Page 72 Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 73: Ten-Year Pro-Rated Limited Warranty (Us And Canada)

    Powerware UPS Models: 5115, 5125, 5140, 9104, 9120, 9125, 9155, 9170+, and FERRUPS ® WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Powerware 5115, 5125, 5140, 9104, 9120, 9125, 9155, 9170+, and FERRUPS Products...
  • Page 74 Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power- ware.com...
  • Page 75: Load Protection Guarantee (Us And Canada)

    Load Protection Guarantee (US and Canada) Powerware UPS Models 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9150, 9155, 9170+, and FERRUPS GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the...
  • Page 76 USA at 919-870-3149. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA. ® EATON Powerware 5125 Two-in-One UPS (2400/3000 VA) User’s Guide 164201383 Rev C www.power-...