SPECIFICATIONS
Table 5. Technical Specifications
Operating Frequency
Frequency Range
Noise Filtering
Input Connections
Regulation
(Normal Mode)
Regulation
(Battery Mode)
Voltage Waveform
Output Receptacles
Table 6. Environmental and Safety
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Heat Dissipation
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
56
EATON Powerware
ware.com
Low Voltage Models
50/60 Hz, auto-sensing
MOVs and line filter for normal and common mode noise
12-ft, L5-30P power cord
-10% to +6% of nominal voltage
Nominal output voltage ±5%
(1) L5-30R, (6) 5-15R
Low Voltage Models
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
5–95% noncondensing
Up to 2,000 meters above sea level
Up to 15,000 meters above sea level
2400 VA: 404.0 BTU/hr (Normal mode); 1572.3 BTU/hr (Battery mode)
3000 VA: 484.9 BTU/hr (Normal mode); 1886.9 BTU/hr (Battery mode)
Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
ANSI C62.41 Category B, IEC 61000-4-5
UL 1778, CSA C22.2, No. 107.1
cULus, cUL
FCC Part 15, ICES-003, VCCI
®
5125 Two-in-One UPS (2400/3000 VA) User's Guide
High Voltage Models
46–64 Hz
12-ft, 16A IEC-309 power cord
PW5125 3000e and 3000g RM models:
16A, IEC 320-C20 input connector
Sine wave
(1) IEC 320-C19, (9) IEC 320-C13
High Voltage Models
UL 1778, CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
cULus, cUL, UL-GS, CE
TÜV-GS (model dependent)
EN 50091-2, FCC Part 15, ICES-003