TROUBLESHOOTING
Alarm or Condition
Continuous audible
alarm.
62
EATON Powerware
ware.com
Possible Cause
Power requirements exceed
UPS capacity (103 to 110% for
30 seconds) or the load is
defective.
The UPS internal temperature
is too high.
Momentary overload.
UPS fault condition.
®
5125 Two-in-One UPS (2400/3000 VA) User's Guide
Action
Turn off and unplug the UPS. Remove some of the
equipment from the UPS. Wait at least five seconds
until all LEDs are off and restart the UPS. You may
need to obtain a larger capacity UPS.
The UPS transfers to Bypass mode, allowing the
UPS to cool. Turn off and unplug the UPS. Clear
vents and remove any heat sources. Ensure the
airflow around the UPS is not restricted. Wait at
least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.
The UPS transfers to Bypass mode. Repeat
overloads will lock on bypass for one hour; press the
|
On
button for immediate return.
Save your work and turn off your equipment. Turn off
and unplug the UPS. Contact your service
representative. The alarm cannot be silenced.