Chapter 7

UPS and Battery Care

Storing the UPS and Batteries

®
EATON Powerware

UPS Maintenance

This section explains how to:
S
Care for the UPS and batteries
S
Replace the electronics module
S
Replace the batteries
S
Recycle used batteries or UPS
For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE If the UPS requires any type of transportation, verify that the UPS is unplugged and
turned off and then disconnect the UPS internal battery connector using the steps in
"Connecting the UPS Internal Battery" on page 20 in reverse order.
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
If you store the UPS for a long period, recharge the batteries every
6 months by plugging the UPS into a power outlet. The batteries charge
to 90% capacity in approximately 3 hours. However, it is recommended
that the batteries charge for 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
5125 Two-in-One UPS (2400/3000 VA) User's Guide
S
164201383 Rev C www.power-
ware.com
47