Eaton 5125 User Manual

Eaton 5125 User Manual

Tower ups 1000–2200 va
Hide thumbs Also See for 5125:

Advertisement

Powerware Series
®
Eaton 5125 Tower UPS
1000–2200 VA
User's Guide

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 5125

  • Page 1 Powerware Series ® Eaton 5125 Tower UPS 1000–2200 VA User's Guide...
  • Page 2 National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ECopyright 2001–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 3 Class A EMC Statements (1000–1500 VA Models) FCC Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 4: Special Symbols

    Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: - Observe the warning associated with the risk of electric shock RISK OF ELECTRIC SHOCK symbol. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
  • Page 5: Table Of Contents

    ............05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 6 ..........05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 7: Introduction

    — causing hours of lost productivity and expensive repairs. With the Eaton 5125, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The Eaton 5125 was designed for critical applications such as PCs, servers, workstations, and telecommunications equipment.
  • Page 8 INTRODUCTION Providing outstanding performance and reliability, the Eaton 5125's unique benefits include: Buck and Double Boost regulation that ensures consistent voltage to your load by correcting voltage fluctuations without using battery power. technology that uses advanced battery management to ®...
  • Page 9: Safety Warnings

    To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 1.5 milliamperes. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 10 I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5 milliampere. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 11: Belangrijke Veiligheidsinstructies

    Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 12 Houd onbevoegden uit de buurt van de accu's. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 13 Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 14 Afin d'être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l'onduleur ne doit pas dépasser 1,5 mA. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 15: Wichtige Sicherheitsanweisungen

    Leitung zu Masseleiter, abhängig von der USV-Verkabelung. Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 16: Avvisi Di Sicurezza

    La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All'interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL'UTENTE. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 17 Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 18: Viktig Sikkerhetsinformasion

    Alt utstyr som er forbundet med utgangen av denne UPS'en må ikke ha en sterkere total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 19 Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto removerá o aterramento de segurança da UPS e do equipamento conectado. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 20 Î Ï À Ñ Í Î Â äàííîì ÈÁÏ èìåþòñÿ ÑÌÅÐÒÅËÜÍÎ ÎÏÀÑÍÛÅ ÍÀÏÐßÆÅÍÈß. Âñå ðàáîòû ïî ðåìîíòó è îáñëóæèâàíèþ äîëæíû âûïîëíÿòüñÿ ÒÎËÜÊÎ ÓÏÎËÍÎÌÎ×ÅÍÍÛÌ ÎÁÑËÓÆÈÂÀÞÙÈÌ ÏÅÐÑÎÍÀËÎÌ. Âíóòðè ÈÁÏ íåò óçëîâ, ÎÁÑËÓÆÈÂÀÅÌÛÕ ÏÎËÜÇÎÂÀÒÅËÅÌ. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 21 Íåîáõîäèìî ñîáëþäàòü ïðàâèëà óòèëèçàöèè àêêóìóëÿòîðîâ. Îáðàòèòåñü ê ìåñòíûì íîðìàòèâíûì àêòàì çà èíôîðìàöèåé î òðåáîâàíèÿõ ê óòèëèçàöèè. Íèêîãäà íå áðîñàéòå àêêóìóëÿòîðû â îãîíü. Àêêóìóëÿòîðû ìîãóò âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 22: Advertencias De Seguridad

    Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 1,5 miliamperios. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 23 är spänningen i de utgående uttagen 115 V (uppmätt från ledare-till-jord eller ledare-till-nolla beroende på UPS:ens anslutning). Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen från både UPS-enheten och den anslutna utrustningen. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 24 Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 25: Installation

    NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 26: Connecting The Ups Internal Battery

    Figure 3. Removing the Battery Cover Remove the protective label from the internal battery connector (see Figure 4). 1000 VA 1500 VA 2200 VA Figure 4. Removing the Protective Label 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 27 1500 VA 2200 VA Figure 5. Connecting the Internal Battery Connector(s) Replace the metal battery cover. Replace the UPS front cover. Continue to the following section, “Installing the UPS.” 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 28: Installing The Ups

    If you plan to install power management software, connect your computer to the UPS communication port using the supplied communication cable. For more information about communication options, see page 35. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 29 24 hours after installation or long-term storage. NOTE If more than two EBMs are installed, an external battery charger is recommended for faster recharge times. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 30: Ups Rear Panels

    INSTALLATION UPS Rear Panels This section shows the rear panels of the Eaton 5125 models. Communication X-Slot Port Communication Network Transient Protector Six 5-15R Battery Receptacles Connector 6‐ft Power Cord with 5‐15 Plug Figure 7. PW5125 1000 and PW5125 1500 Rear Panel...
  • Page 31 Figure 9. PW5125 1000i and PW5125 1500i Rear Panel Communication Port X-Slot Network Transient Communication Protector Nine 10A, IEC 320-C13 Receptacles Battery Connector 10A, IEC‐320 Input Connector Figure 10. PW5125 2200i Rear Panel 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 32 Figure 11. PW5125 1000j Rear Panel Communication X-Slot Port Communication Network Transient Protector Six 5-15R Battery Receptacles Connector 6‐ft Power Cord with 5‐20 Plug Figure 12. PW5125 1500j Rear Panel 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 33 Figure 13. PW5125 2200j Rear Panel Communication Port X-Slot Network Transient Communication Protector Nine 10A, IEC 320-C13 Receptacles Battery Connector 15A, IEC‐320 Input Connector Figure 14. PW5125 2200b Rear Panel 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 34 INSTALLATION 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 35: Operation

    To turn on the UPS without using utility power, press and hold the On button for at least four seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 36: Turning The Ups Off

    During the test, individual indicators illuminate as various parts of the UPS are checked. If the alarm beeps or a UPS alarm indicator stays on, see Table 9 on page 54. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 37: Operating Modes

    OPERATION Operating Modes The Eaton 5125 front panel indicates the UPS status through the UPS indicators. Figure 15 shows the UPS front panel indicators and controls. Indicator Legend Unlit Green On Button Flashing Off Button Test/Alarm Reset Button Battery Mode Indicator...
  • Page 38: Normal Mode

    Buck, Single Boost, or Double Boost mode as shown in Figure 17. Buck Mode Single Boost Mode Double Boost Mode Figure 17. Buck and Double Boost Indicators 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 39: Battery Mode

    The battery recharges when necessary. NOTE For 230V models, the output receptacles may remain electrically live (up to 115V). Unplug the UPS to ensure power is not available to the output receptacles. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 40 OPERATION 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 41: Additional Ups Features

    X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 5125 is factory-installed with a Single-Port Card, which can be replaced with one of the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
  • Page 42: Single-Port Card

    USB Card Figure 18. Optional X-Slot Cards Single-Port Card The Eaton 5125 is factory-installed with a Single-Port Card, enabling connection to a PC for power management control or to the Expansion Chassis for multiple communication options. To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
  • Page 43 PnP from external device In / Out AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Power Source +V (8 to 24 volts DC power) 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 44: Network Transient Protector

    Connect the input connector of the equipment you are protecting to the jack labeled IN. Connect the network or telephone (low voltage models only) cable to the jack labeled OUT. Figure 20. Network Transient Protector 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 45: Load Segments

    100V/120V Models 208V/230V Models Load Segment 1 Load Segment 1 Load Segment 2 Load Segment 2 Load Segment 3 Load Segment 3 Figure 22. 2200 VA Load Segments 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 46 ADDITIONAL UPS FEATURES 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 47: Ups Maintenance

    Verify that the UPS is unplugged and turned off. Disconnect the UPS internal battery connector using the steps in “Connecting the UPS Internal Battery” on page 20 in reverse order. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 48: Storing The Ups And Batteries

    2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries. ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 49: How To Replace Internal Batteries

    Figure 23. Removing the UPS Front Cover Slide up and remove the metal battery cover (see Figure 24). 1000 VA 1500 VA 2200 VA Figure 24. Removing the Battery Cover 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 50 See “Recycling the Used Battery or UPS” on page 47 for proper disposal. Black Battery Cable Red Battery Cable Figure 25. Battery Removal (1000 VA Models) 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 51 Figure 26. Battery Removal (1500 and 2200 VA Models) Install the new batteries in the reverse order of removal. Replace the metal battery cover. Replace the UPS front cover. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 52: How To Replace Extended Battery Modules

    After the test is finished, the indicator should turn off. If the indicator stays on, check the battery connections. Call your service representative if the problem persists. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 53: Recycling The Used Battery Or Ups

    C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 54 UPS MAINTENANCE 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 55: Specifications

    2200 VA Models 20.5 49.3 25.0 cm (8.07” 19.41” 9.84”) 31 kg (68 lb) Extended Battery Module 16.2 47.4 25.0 cm (6.38” 18.66” 9.84”) 27 kg (60 lb) (EBM) 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 56 MOVs and line filter for normal and common mode noise Regulation -10% to +6% of nominal voltage (Normal Mode) Regulation Nominal output voltage ±5% (Battery Mode) Voltage Waveform Sine wave 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 57 EBMs. Monitoring Advanced monitoring for earlier failure detection and warning; auto detection of additional EBMs 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 58 1500 VA 6/17 33/79 63/146 92/174 120/201 2200 VA 5/14 26/60 55/170 81/198 106/224 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 59: Troubleshooting

    Indicator Legend Unlit Green On Button Flashing Off Button Test/Alarm Reset Button General Alarm On Battery Battery Service Site Wiring Fault Power On Figure 28. Alarm Indicators 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 60: Silencing An Audible Alarm

    Press and hold the button for 3 seconds. If the indicator is still on, see “Replacing Batteries” on page 42. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 61 “Replacing Batteries” on page 42. The battery is not connected Check the b attery connections. Call your correctly. service representative if the problem persists. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 62 UPS. UPS fault condition. Save your work and turn off your equipment. Turn off and unplug the UPS. Contact your service representative. The alarm cannot be silenced. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 63: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 64 TROUBLESHOOTING 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 65: Warranty

    This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 3105, 5110, 5115, 5125, and 5130 Products (individually and collectively, the “Product”) purchased on or after August 19, 2009 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
  • Page 66 Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. 05147304 Rev C www.eaton.com/powerquality Eaton 5125 Tower UPS (1000–2200 VA) User's Guide...
  • Page 67: Load Protection Guarantee (Us And Canada)

    In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, call your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.