Algorithm Set Up Group; Table 3-7 Algor Group (Numeric Code 400) Function Prompts - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration

3.7 Algorithm Set Up Group

Introduction
This data deals with various algorithms in the controller and Timer functions.
The Timer section allows you to configure a time-out period and to select the timer start
by either the keyboard (
configured to the start the timer. The timer display is selectable as either "time
remaining" (see TREM) or "elapsed time" (see ET).
Alarm 1 is activated at the end of the time-out period. When the timer is enabled, it has
exclusive control of the alarm 1 relay—any previous alarm 1 configuration is ignored. At
time-out, the timer is ready to be activated again by whatever action has been configured.
Function Prompts

Table 3-7 ALGOR Group (Numeric Code 400) Function Prompts

Function Prompt
Lower Display
English
Numeric
Code
CTRALG
401
46
key) or Alarm 2. An optional digital input can also be
RUN/HOLD
Selection or Range of Setting
Upper Display
English
Numeric
ONOF
UDC2500 Universal Digital Controller Product Manual
Code
The CONTROL ALGORITHM lets you select
the type of control that is best for your
process.
ON/OFF is the simplest control type. The
0
output can be either ON (100 %) or OFF (0
%). The Process Variable (PV) is compared
with the setpoint (SP) to determine the sign
of the error (ERROR = PV–SP). The
ON/OFF algorithm operates on the sign of
the error signal.
In Direct Acting Control, when the error
signal is positive, the output is 100 %; and
when the error signal is negative, the output
is 0 %. If the control action is reverse, the
opposite is true. An adjustable overlap
(Hysteresis Band) is provided between the
on and off states.
ATTENTION Other prompts affected:
OUTHYS
Parameter
Definition
4/07