Table 5-8 Set Up Wiring Procedure For 0 To 10 Volts; Table 5-9 Set Up Wiring Procedure For Milliampere Inputs; Figure 5-6 Wiring Connections For 0 To 10 Volts; Figure 5-7 Wiring Connections For 0 To 20 Ma Or 4 To 20 Ma Inputs - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

0 to 10 Volts
Refer to Figure 5-6 and wire the controller according to the procedure given in Table 5-8.
Step
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
1
Figure 5-6.
Place voltage source at zero before switching on.
2
3
Do not switch voltage source ON/OFF while connected to the instrument.
Milliamperes
Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-7.

Table 5-9 Set Up Wiring Procedure for Milliampere Inputs

Step
1
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-7.
2
Place current source at zero before switching on.
3
Do not switch current source ON/OFF while connected to the instrument.

Figure 5-7 Wiring Connections for 0 to 20 mA or 4 to 20 mA Inputs

4/07

Table 5-8 Set Up Wiring Procedure for 0 to 10 Volts

Volt
Volt
Source
Source

Figure 5-6 Wiring Connections for 0 to 10 Volts

+
+
Milliampere
Milliampere
Source
Source
_
_
UDC2500 Universal Digital Controller Product Manual
Action
+
+
1
1
2
2
100K pair
100K pair
_
_
3
3
Action
250 ohms
250 ohms
Input Calibration
26+
26+
27-
27-
26+
26+
27-
27-
143