Table 5-13 Input 2 Calibration Procedure (Numeric Code 20000) - Honeywell UDC2500 Product Manual

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Input Calibration
Procedure
The calibration procedure for Input #2 is listed in Table 5-13. The numeric codes are also
listed.

Table 5-13 Input 2 Calibration Procedure (Numeric Code 20000)

Step
Operation
Enter Calibration
1
Mode
2
Calibrate 0 %
3
Calibrate 100 %
4
Exit the
Calibration Mode
148
Press
Upper Display = CAL (
Setup
Setup
Lower Display = INPUT2 (20000)
until you see
You will see:
Function
Function
Function
Upper Display = DIS ( 0 )
Lower Display = CALIN2 (20001)
You will see:
or
Upper Display = BEGN ( 1 )
Lower Display = CALIN2 (20001)
You will see:
Function
Function
Function
Upper Display = APLY ( 2 )
Lower Display = IN2ZRO (20002)
Adjust your calibration device to an output signal equal
to the 0 % range value for your particular input sensor.
Wait 15 seconds, then go to the next step.
You will see:
Function
Function
Function
Upper Display = APLY ( 2 )
Lower Display = IN2SPN (20003)
Adjust your calibration device to an output signal equal
to the 100 % range value for your particular input
sensor.
Wait 15 seconds, then go to the next step.
The controller stores the calibration constants.
Function
Function
Function
To store the calibration constants and exit the calibration
Lower
Lower
Lower
mode.
Display
Display
Display
UDC2500 Universal Digital Controller Product Manual